proCHEM-P pH Controller
with Dual Set Points

|
|

Full Size Picture |
 | Enclosure Waterproof to IP65
|
 | Dual Set Point Control Relays
|
 | Earth Current Rejection
|
 | Easy to Install
|
 | Easy to Use
|
 | 4-20mA and 0-1 V DC Outputs
|
 | Australian Made |
|
| The NEW proCHEM
Series controllers provide an
economical answer to most process monitoring, control or
recording requirements.
Dual Set Points are provided. The default setup for these are as
"Too High" and "Too Low" control points. The
user can also re-set them so that they are both "Too High" or
both "Too Low" control points. An example of this type of setup
is where the proCHEM unit has one point set to control the
process, and a second point beyond that set to activate an alarm.
Separate LED's indicate when either of the Set Points has been
exceeded. The output relays are rated to 240V and are fused at 2 Amps.
Higher currents can be switched with an external contactor.
All proCHEM units are easy to install. They are housed in a
rugged plastic case which is non corrosive, waterproof and dustproof to
IP65. All controls
can be accessed via the hinged, clear cover. The large LCD display is easy
to read, even from a distance. |
The proCHEM series is designed for maximum
flexibility. 4 to 20 mA and
0 to 1 V DC outputs are provided as standard.
For even greater output
flexibility, ask about the 420 ToolBox. This module provides
such features as reversing the current or voltage signal, and optional
extra control relay, RS232 interface or pulsed output.
For a total solution to your control requirements, TPS also offers a
range of Peristaltic Pumps.
The proCHEM series is proudly designed and manufactured
in Australia. The TPS Quality System has been certified in accordance with
AS/NZS ISO9001 standards. Since 1968, TPS has built a reputation for excellent backup
service that is second to none. |

Specifications
|
Range
0 to 14.00 pH
Resolution
0.01 pH
Accuracy
+/-0.01 pH
Linearity
+/-0.01 pH
Repeatability
+/-0.01 pH
Ambient Drift
<0.01 pH per 10OC
change
Long Term Drift
<0.1% per year
Temperature Compensation
Automatic, 0 to 100 OC
Asymmetry Range
+/-1 pH
Slope Range
80 to 110%
Input Impedance
>3 x 1012 Ohms
Common Mode Rejection
120dB |
Enclosure
Polycarbonate, waterproof to
IP65
Display
12.5mm LCD
Outputs
Current : 4 to 20 mA
Voltage : 0 to 1 V DC
Contacts : Two relays with changeover
contacts.
Rated to
240V, 1 Amp
Isolation
Galvanic isolation of sensor
input
Current and voltage outputs
are not
isolated
Power
220/240 V AC, 50/60Hz, 2VA
12V DC power optional.
Dimensions
215 x 190 x 115 mm
Mass
Instrument only : Approx 900g
Full Kit
: Approx 1.5kg
Instrument Operating Environment
Temperature : 0 to 45 OC
Humidity : 0
to 95% R.H. |

Ordering Information
|
Part No
proCHEM-P Controller........111122
Kit Includes
proCHEM-P Handbook..........130050
pH6.88 Buffer, 200mL........121306
pH4.00 Buffer, 200mL........121381 "Dip"
mounted sensors and
submersible assembly...
Submersible pH, 5m..........111228
ATC Probe, 5m...............111275
Submersible Assembly........111303 Screw-in
sensors and 40mm
pipe adaptor...
Screw-in pH, 5m.............111244
Screw-in ATC Probe, 5m......111265
Probe to 40mm Pipe..........111305
Adaptor |
Part No
Options
Extended cable..............130040
(order by the metre)
12V DC Power option.........130072
Remote, 2-wire 4-20mA
Loop..130080
Powered LCD Display
|
|

|
Download this Specification Sheet in PDF format.
Download the full colour proCHEM Series Brochure (433 KB PDF).
Download the handbook for
this instrument.
Hint : Right click on a link, then
select "Save Target As..." or "Save Link As..." to save
the file to your own computer.
If you do not have Adobe Acrobat in your computer, a free Acrobat
Reader can be downloaded by clicking on the following link.
|
TPS reserves the right to change any part of this
specification without notice.
Version 1.0
Copyright © 2003 T.P.S. Pty Ltd |