TPS_Logo.gif (100759 bytes)   


 

TPS Australia - Quality instruments since 1968.

proCHEM-C Conductivity Controller 
with Dual Set Points

Full Size Picture

bulletEnclosure Waterproof to IP65

bulletDual Set Point Control Relays

bulletEasy to Install

bulletEasy to Use

bullet4-20mA and 0-1 V DC Outputs

bulletAustralian Made
The NEW proCHEM Series controllers provide an economical answer to most process monitoring, control or recording requirements.

Dual Set Points are provided. The default setup for these are as "Too High" and "Too Low" control points.  The user can also re-set them so that they are both "Too High" or both "Too Low" control points. An example of this type of setup is where the proCHEM unit has one point set to control the process, and a second point beyond that set to activate an alarm.

Separate LED's indicate when either of the Set Points has been exceeded. The output relays are rated to 240V and are fused at 2 Amps. Higher currents can be switched with an external contactor.

All proCHEM units are easy to install. They are housed in a rugged plastic case which is non corrosive, waterproof and dustproof to IP65. All controls can be accessed via the hinged, clear cover. The large LCD display is easy to read, even from a distance.

The proCHEM series is designed for maximum  flexibility. 4 to 20 mA and 
0 to 1 V DC outputs are provided as standard.

For a total solution to your control             requirements, TPS also offers a peristaltic pump, the easyFLOW-VS.

The proCHEM series is proudly designed and manufactured in Australia. The TPS Quality System has been certified in accordance with AS/NZS ISO9001 standards. Since 1968, TPS has built a reputation for excellent backup service that is second to none.


Specifications

Ranges
k=0.1 Sensor....0 to 19.99 uS/cm
                0 to 199.9 uS/cm
                0 to 1999  uS/cm
k=1.0 Sensor....0 to 199.9 uS/cm
                0 to 1999  uS/cm
                0 to 19.99 mS/cm
k=10 Sensor.....0 to 1999  uS/cm
                0 to 19.99 mS/cm
                0 to 199.9 mS/cm

Resolution
0.1% of full scale

Accuracy
+/-0.2% of full scale at 25 OC

Linearity
+/-0.05% of full scale

Repeatability
+/-0.05% of full scale

Ambient Drift
<0.02%/OC

Long Term Drift
<0.1% per year

Temperature Compensation
Automatic, 0 to 100OC

Zero Range
+/-5%

Span Range
70 to 130%

Sensors
Platinised Platinum,
k=0.1, k=1.0 or k=10

Enclosure
Polycarbonate, waterproof to IP65

Display
12.5mm LCD

Outputs
Current  : 4 to 20 mA
Voltage  : 0 to 1 V DC 
Contacts : Two relays with changeover
           contacts.
           Rated to 240V, 1 Amp

Isolation
Galvanic isolation of sensor input

Current and voltage outputs are not
isolated

Power
220/240 V AC, 50/60Hz, 2VA

12V DC power optional.

Dimensions
215 x 190 x 115 mm

Mass
Instrument only : Approx 900g 
Full Kit        : Approx 1.5kg

Instrument Operating Environment
Temperature : 0 to 45 OC
Humidity    : 0 to 95% R.H


Ordering Information

                                               Part No

5 metre bundle 112126/5:
proCHEM-
Conductivity, 5m.......................112126/5

5 metre Option Includes:
k=1 Cond-ATC sensor 5m, plastic................112206
Conductivity standard to suit customer-specified range
Manual.........................................130050

Options and Accessories


Cable Extension:
Extended cable/metre...........................130040

Instrument Options:
12V DC Power option............................130072
Sensor flow chamber: 1/2" BSP in/out ports.....111303

Same Price Interchange Option:
Choose between k=0.1, k=1 and k=10 Range Conductivity Sensors

k=10  Cond-ATC sensor 5m, plastic..............112207
k=0.1 Cond-ATC sensor 5m, plastic.....
.........112205

Download this Specification Sheet in PDF format.

Download the full colour proCHEM Series Brochure (433 KB PDF).

Download the manual for this instrument.

Hint : Right click on a link, then select "Save Target As..." or "Save Link As..." to save the file to your own computer.

If you do not have Adobe Acrobat in your computer, a free Acrobat Reader can be downloaded by clicking on the following link.

 

TPS reserves the right to change any part of this specification without notice.
Version 1.0
Copyright © 2003 T.P.S. Pty Ltd
 